Honeywell S89E1058 Two-rod direct spark ignition control with 4 sec. trial time and lock out timingOverview
Provide electronic control of direct spark ignition systems, with external spark transformers, used on gas-fired furnaces, boilers, conversion burners and other heating appliances.
Features
- Controls ignition sequence and gas control operation in direct spark ignition systems.
- Control separate 120 Vac spark generator that provides high voltage potential for main burner ignition.
- Lockout after one trial for ignition if main burner fails to ignite.
- Reset from thermostat after lockout. Use separate electrodes for spark ignition and flame sensing.
- Use any 24 Vac combination gas control designed for direct spark applications and rated at 2.0A or less.
Product Specifications | |
Dimensions (in.) | 5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long |
Dimensions (mm) | 133 mm high x 103 mm wide x 49 mm deep |
Electrical Ratings | 24 Vac |
Frequency | 60 Hz |
Approvals, Canadian Standards Association | Design Certified |
Flame Failure Response Time (sec) | 2.0 sec. @ 2.5 microamp |
Ambient Temperature Range (F) | -40 F to +175 F |
Ambient Temperature Range (C) | -40 C to +79 C |
Ignition System Type | Direct Spark Ignition |
Ignition Sequence | Single trial for main burner ignition (then shut down and lockout) |
Typical Gas Control | VR8205, VR8305 |
Type of Gas | Natural or LP |
Flame Sense | Two Rod |
Ignition Source | External (120 VAC powered) High Voltage Spark Generator |
Ignition Trials To Lockout | 1 |
Lockout Timing | 4 sec. |
Ignition Trial Time (sec) | 4 sec. |
Maximum Valve Load @ 24 Vac (Amps) | 2A |
Flame Failure Re-ignition Time (sec) | 0.8 sec. maximum |