Overview The FSP5075A Flame Amplifier Modules accept various Honeywell plug-in flame signal amplifiers. Depending on the type, the flame amplifier module work with ultraviolet flame detectors, infrared flame detectors, rectifying flame rods or photocells. Features The flame amplifier module amplifier and relay circuitry combine to provide such safety features as safe-start check, safety shutdown and rapid flame failure response time. Approval body certifications include Underwriters Laboratories Inc. component recognized, Factory Mutual approved and Swiss RE approvable. The zinc dichromate finish resists corrosive effects of most industrial atmospheres. A hermetically sealed relay model is also available. The FSP5075A Flame Amplifier Module is a standard building block in a burner management system. It allows the system to meet flame safeguard requirements while adding versatility to the flame detection system. Product Specifications ApplicationFlame AmplifierDimensions (in.)4 7/8 in. high x 8 1/2 in. wide x 4 in. deep.Dimensions (mm)124 mm high x 216 mm wide x 102 mm deepTemperature Range (F)-40 F to +140 FTemperature Range (C)-40 C to +60 CUsed WithR7247, R7248, R7249, or R7476 Flame AmplifierComments Relaysjavascript:void(0); Plastic SealedFrequency60 HzApprovals, Underwriters Laboratories Inc.Component Recognized: File No. MP268, Guide No. MCCZVoltage120 Vac; Power Consumption--5.0 W running (max); 2.4 W standby.Flame Failure Response Time (sec)Reference flame signal amplifierApprovals, Swiss REAcceptableApprovals, Factory MutualApproved: Report No. 26098