Product Description
Honeywell W7215A1006 Series 72 economizer logic module with analog input from one IAQ sensorOverview
Use with C7400A, or C7660 and C7150B or C7046 Sensors; Demand Control Ventilation (DCV) sensor C7232 C02 sensor (2-10 Vdc); and Honeywell Series 72 actuators, or M7415 Damper Actuator to proportion outdoor and return air dampers for economizer and ventilation control in commercial HVAC equipment. (See below)
.
Features
- Input from DCV C02 sensor provides optimum ventilation based on occupancy.
- Includes air change and shutdown.
- Demand control ventilation economizer provides comfort, energy savings, reliability, air quality compliance and application flexibility in heating, cooling and ventilating applications.
- Combines enthalpy or dry bulb changeover control, minimum and maximum damper position potentiometer and DCV setpoint functions.
- Optional differential enthalpy control (enthalpy setpoint D with two C7400A sensors) provides greater economizer savings and maximum comfort over single enthalpy control.
- Enthalpy setpoint (A-D) on economizer module controls the combination of air temperature and humidity that is suitable for free cooling.
- LEDs indicates when economizer is in free cooling and DCV modes.
- Provides for input from an outdoor air quality sensor.
Product Specifications | |
Dimensions (in.) | 8 11/16 in. high x 5 13/16 in. wide x 1 11/16 in. deep |
Dimensions (mm) | 221 mm high x 147 mm wide x 43 mm deep |
Used With | Honeywell Series 72 actuators |
Comments | Can accept remote minimum position damper position potentiometer and/or analog input from one carbon dioxide sensor for indoor air.; Economizer Logic Module operates Series 72 actuators. |
Frequency | 50 Hz; 60 Hz |
Approvals, Underwriters Laboratories Inc. | UL Listed File: E4436, Guide: XAPX, Meets UL873 plenum requirements |
Operating Humidity Range (% RH) | 5 to 95% RH, non-condensing |
Contact Ratings | 30 Vac-- 1.5 A Run, 3.5 A Inrush |
Voltage | 24 Vac |
Operating Temperature Range (F) | -25 F to +125 F |
Operating Temperature Range (C) | -32 C to +52 C |
Approvals, CE | CE Report: GV02-003 |
Output | 2-10 Vdc to actuator |
Use with Sensor | C7150; C7046; C7232; C7400A; C7660 |
Input | Air Quality Sensor; Discharge Air Temperature sensor: C7150 or C7046 |
Approvals, Others | Complies with California Title 24 |
Approvals, C-Tick | Approved |