Product Description
Honeywell TP971A2102 Pneumatic Thermostat Direct Acting HeatingOverview
Two-pipe, one- or two-temperature, pneumatic thermostat gives proportional control of pneumatic valves & damper actuators. Replacement kits available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell two-pipe pneumatic thermostats.
Feature
- Durable TP970 Series Thermostat. Pilot operated for high capacity.
- Two-temperature energy conservation model available.
- Adapter plate in Convertastatâ„¢ kits covers existing thermostat wall mark.
- Backplate has molded air connections-no separate fittings needed.
- Universal locking cover with satin chrome finish and horizontal, vertical, or blank window options with Tradeline model-other covers available.
Product Specifications | |
Application | Wall Thermostat, Day/Night operation |
Airflow Usage | 0.011 scfm (5.2 mL/s) |
Dimensions (in.) | 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep |
Dimensions (mm) | 83 mm high x 51 mm wide x 41 mm deep |
Maximum Safe Operating Pressure (psi) | 25 psi |
Maximum Safe Operating Pressure (kPa) | 170 kPa |
Temperature Range (F) | 100 F maximum |
Includes | Thermostat, small wall plate and satin chrome cover. |
Comments | Convertastat Kit |
Mounting | Wall mount |
Approvals, Underwriters Laboratories Inc. | N/S |
Approvals, Canadian Standards Association | N/S |
Setpoint Temperature Range (F) | Day: 59 F to 90 F, Night: 50 F to 80 F |
Shipping and Storage Temperature Range (F) | 150 F maximum |
Shipping and Storage Temperature Range (C) | 66 C maximum |
Approvals, Factory Mutual | N/S |
Sensor Element | Bimetal |
Throttling Range (F) | 2 F to 10 F |
Throttling Range (C) | 1 C to 5 C |
Connection Size (in.) | N/S |
Differential Pressure Range (psi) | N/S |
Differential Pressure Range (kPa) | N/S |
Approvals, NEMA Standard | N/S |
Action | Direct Acting Heating, two temp. |
Setpoint | Day/Night |
Number of Pipes | 2 |
Changeover Pressure (psi) | Day 13 psi, Night 18 psi or 16-20 psi |
Changeover Pressure (kPa) | Day 90 kPa, Night 124 kPa |
Mainline Pressure Range (psi) | N/S |
Capacity | N/S |
Control Range (fpm) | N/S |
Control Range (m/s) | N/S |
Number of Sensor Inputs | N/S |
Remote Control Point Adjustment | N/S |
Approximate Throttling Range, Midscale (psi) | N/S |
Approximate Throttling Range, Midscale (kPa) | N/S |