Product Description
Honeywell T991A1012 Modulating Temperature Controller, 0 - 100 F. 20' copper element. max. Operating Temperature: 125FOverview
Proportional (135 ohm) remote bulb controllers for modulating control of water or air temperature in ducts, tanks and similar applications.
Feature
- Fast response models (for duct mounting) have coiled sensing element giving at least four times faster response than standard models.
- Ambient temperature compensated for the case and tubing.
- Sensing element capillary tubing allows remote mounting of sensing element.
- Setpoint may be read and adjusted through cover.
- Throttling dial inside case adjusts proportional throttling range.
Product Specifications | |
| Hazmat Information | UN 1993 Flammable liquid, n.o.s. |
| Application | Provide modulating control of water or air temperature in ducts or tanks |
| Dimensions (in.) | 5 5/8 in. high x 2 in. wide x 2 1/4 in. deep |
| Dimensions (mm) | 143 mm high x 51 mm wide x 57 mm deep |
| Frequency | 50 Hz; 60 Hz |
| Voltage | 24 Vac to 30 Vac |
| Setpoint Temperature Range (C) | -18 C to +38 C |
| Setpoint Temperature Range (F) | 0 F to 100 F |
| Operating Temperature Range (F) | 125 F Maximum |
| Operating Temperature Range (C) | 52 C Maximum |
| Type | Modulating Remote bulb |
| Output | analog |
| Analog Output | One 135 Ohm Potentiometer |
| Sensor Inputs | 1 |
| Sensor Element | Copper bulb |
| Capillary Length (ft) | 20 ft |
| Capillary Length (m) | 6.1 m |
| Bulb Size (in.) | 1/2 in. diameter x 4 3/16 in. long |
| Bulb Size (mm) | 13 mm diameter x 107 mm long |
| Throttling Range (F) | 3 F to 30 F |
| Throttling Range (C) | 1.7 C to 16.7 C |
| Color | Gray |