Product Description
UV DECTECTOR 6 FTOverview
Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers. .
Features
- Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection.
- Mounts on a 1 in. sighting pipe by using an integral collar.
- Protects the sensing tube with a shield.
- Meets outdoor rain tight requirements of Underwriters Laboratories Inc., NEMA 4 and NEMA 4X.
- Wires in parallel for difficult sighting applications.
- Seals against pressures as high as 5 psi (34.5 kPa) when correctly installed.
- Field-replaceable ultraviolet sensing tube.
Product Specifications | |
| Application | Coal fired burners; Gas fired burners; Oil fired burners |
| Dimensions (in.) | 1 1/2 in. diameter x 4 1/8 in. long |
| Dimensions (mm) | 38 mm diameter x 105 mm long |
| Includes | 600F leads |
| Used With | Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290 |
| Weight (lb) | 6 oz |
| Weight (kg) | 0.17 kg |
| Comments | Detects ultraviolet radiation in flames |
| Mounting | Integral nut for 1 in. sighting pipe. |
| Approvals, Underwriters Laboratories Inc. | Listed: File No. MP268, Guide No. MCCZ |
| Approvals, Canadian Standards Association | Certified: Master Report LR95329-1 |
| Electrical Connections | 2 NEC Class 1 lead wires |
| Vibration | 0.5 G max |
| Approvals, Swiss RE | Acceptable |
| Approvals, Factory Mutual | Approved: Report No. 24181.03 |
| Type | Ultraviolet, Minipeeper |
| Ambient Temperature Range (F) | 0 F to 250 F |
| Ambient Temperature Range (C) | -18 C to +121 C |
| NEMA Rating | NEMA 3 and NEMA 4 |
| Lead Length (in.) | 72 in. |
| Lead Length (mm) | 1829 mm |