Product Description
Honeywell C7027A1080 Flame Sensor, Ultraviolet, MinipeeperOverview
Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers.
Features
- Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection.
- C7027 mounts on a 1/2 in. sighting pipe by using an integral collar.
- Detectors can be wired in parallel for difficult sighting applications.
- C7027 seals against pressures up to 5 psi (34.5kPa) when correctly installed.
- Allows for blast tube mounting due to compact size.
- C7044 mounts with a two screw bracket.
- The C7044 UV sensor tube is enclosed in a stainless steel housing.
- C7044 has the capability of side or end viewing in flame monitoring applications.
Product Specifications | |
Application | Coal fired burners; Gas fired burners; Oil fired burners |
Dimensions (in.) | 1 1/16 in. diameter x 4 in. long |
Dimensions (mm) | 27 mm diameter x 102 mm long |
Includes | 136733 Heat Block and 390427B bushing |
Used With | Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290 |
Comments | Detects ultraviolet radiation in flames |
Mounting | Integral nut for 1/2 in. sighting pipe. |
Approvals, Underwriters Laboratories Inc. | Listed: File No. MP268, Guide No. MCCZ |
Approvals, Canadian Standards Association | Certified: Master Report LR95329-1 |
Electrical Connections | 2 NEC Class 1 lead wires |
Vibration | 0.5 G max |
Approvals, Swiss RE | Acceptable |
Approvals, Factory Mutual | Approved: Report No. 24181.03 |
Type | Ultraviolet, Minipeeper |
Ambient Temperature Range (F) | 0 F to 215 F |
Ambient Temperature Range (C) | -18 C to +102 C |
Lead Length (in.) | 96 in. |
Lead Length (mm) | 2438 mm |