Product Description
30 Sec Purge, 10 Sec PTFI/MTFI Term 5 and 10 Sec PTFI/15 Sec MTFI Term 6 Ignition, 4 Sec Flame Failure Response, Recycle, Selectable Purge, Burner Management Control Programmer Module The Programmers Provide Start-Up Programming, Safe-Start Check and Flame Monitoring Supervision
• They Insure Proof of Low Fire Position and Fuel Valve End Switch Safety Checks
• The Control is Designed to Initiate a Safety Lockout If any of these Circuits are Open at the Improper Point in the Control Cycle
• a Running Interlock Circuit on the Flame-Monitor System Constantly Monitors the Limit Switches, Air Flow Switches and Fuel Pressure Switches through the Programmer
• The Programmer will Recycle If the Running Interlock Circuit (3-P) is Opened During the Firing Cycle"" • Burner Management Control Programmer Module
• Item Programmer Module
• Type Recycle, Selectable Purge
• Purge Time 30 Second
• Ignition Time 10 Second (PTFI/MTFI) for Term 5, 10 Second PTFI, 15 Second (MTFI) for Term 6
• Flame Failure Response Time 4 Second
• Used On Flame Monitor Burner Management Control
• Approval UL (Canada and US), FM • Type Recycle, Selectable Purge
• Purge Time 30 Second
• Ignition Time 10 Second (PTFI/MTFI) for Term 5, 10 Second PTFI, 15 Second (MTFI) for Term 6
• Flame Failure Response Time 4 Second
• Used On Flame Monitor Burner Management Control
• Approval UL (Canada and US), FM