Description: IPI Gas Ignition Control - replacement for popular models, including York 025-27762-700 and JCI G770RJA-1 series controls Intermittent pilot gas ignition control For use with intermittent pilot boilers, furnaces and other heating appliances Microprocessor-based precision Monitors timing, trial for ignition, rollout switch, flame sensing and lockout Remote flame sensing 100% lockout safety feature Works with both Natural and LP gas systems Specifications: Control Voltage: Line 24V (18-30 VAC), 50/60Hz Anticipator Setting: 0.2A plus valve load @ 24VAC Prepurge: None Trial for Ignition: 85 seconds Flame Failure Response Time: 0.5 seconds Retry: None Weight/Dimensions: Weight: 0.45 Height: 2 Width: 5.375 Length: 4ReplacesJohnson Controls: G770RJA-1York: 025-27762-700 Â